CVE-2023-38123
Inductive Automation Ignition OPC UA Quick Client Missing Authentication for Critical Function Authentication Bypass Vulnerability
CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H
Fuente: CNA
Ciclo de vida de la vulnerabilidad
| Fecha | Fase | Evento | Detalle |
|---|---|---|---|
| Divulgación | Publicada | CVE-2023-38123 divulgada · CVSS 7.5 (CNA) | |
| Divulgación | Evaluación SSVC | CISA-ADP · explotación ninguna | |
| Divulgación | Modificada | Última actualización del registro | |
| Monitoreo | Detectada | Ingresó al índice |
Inductive Automation Ignition OPC UA Quick Client Missing Authentication for Critical Function Authentication Bypass Vulnerability. This vulnerability allows remote attackers to bypass authentication on affected installations of Inductive Automation Ignition. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file. The specific flaw exists within the server configuration. The issue results from the lack of authentication prior to allowing access to password change functionality. An attacker can leverage this vulnerability to bypass authentication on the system. Was ZDI-CAN-20540.
Desglose de métricas
Versiones afectadas
8.1.24Estado del parche por paquete
| Paquete / producto | Estado | Corregida en | Desde divulgación | Última versión |
|---|---|---|---|---|
Ignition |
Sin parche | — | — | — |
Arsenal público
Sin exploits, módulos ni PoC públicos conocidos a la fecha de verificación.
https://inductiveautomation.com/blog/inductive-automation-participates-in-pwn2own-to-strengthen-ignition-securityhttps://www.zerodayinitiative.com/advisories/ZDI-23-1014/Las referencias externas se muestran para copiar: cve.llama.ec no lo redirige a otros sitios.