CVE-2026-4769
Unauthenticated Access to Internal Diagnostic Interface
CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N
Fuente: CNA
Ciclo de vida de la vulnerabilidad
| Fecha | Fase | Evento | Detalle |
|---|---|---|---|
| Divulgación | Publicada | CVE-2026-4769 divulgada · CVSS 9.3 (CNA) | |
| Divulgación | Evaluación SSVC | CISA-ADP · explotación ninguna | |
| Divulgación | Modificada | Última actualización del registro | |
| Monitoreo | Detectada | Ingresó al índice |
Certain devices in the WAGO System I/O Field series activate an internal diagnostic capability during the initial startup sequence. This functionality is not formally documented and becomes accessible without authentication for a brief period in the early boot phase. During this window, an unauthenticated remote attacker can gain access to the internal system processes, resulting in full system compromise.
Desglose de métricas
Rangos afectados
Estado del parche por paquete
| Paquete / producto | Estado | Corregida en | Desde divulgación | Última versión |
|---|---|---|---|---|
0765-110x/0100-0000 |
Corregida | 1.2.1.100 | — | — |
0765-120x/0100-0000 |
Corregida | 1.2.7.100 | — | — |
0765-150x/0100-0000 |
Corregida | 1.2.7.103 | — | — |
0765-2101/0100-0000 |
Corregida | 1.2.1.102 | — | — |
0765-2102/0100-0000 |
Corregida | 1.2.5.101 | — | — |
0765-410x/0100-0000 |
Corregida | 1.2.1.100 | — | — |
0765-420x/0100-0000 |
Corregida | 1.2.7.100 | — | — |
0765-450x/0100-0000 |
Corregida | 1.2.7.103 | — | — |
1.2.1.1001.2.1.1021.2.5.1011.2.7.1001.2.7.103Arsenal público
Sin exploits, módulos ni PoC públicos conocidos a la fecha de verificación.